Amp-Trap 2000® SmartSpot time-delay A6D-R fuses provide IEC Type 2 "no damage" protection to existing mains, feeders, and branch circuits serving motor and non-motor loads. A6D-R fuses will open fast enough under extreme fault conditions for maximum short circuit protection to prevent damage to motor starters, switches, and other circuit components, yet also provide the time-delay needed for motor in-rush currents. A6D-R fuses can be used to replace older 600V Class H, K or RK5 fuses already installed in the field.

Technical Information

Amperage
40 Amp
Applications
For Motors, Safety Switches, Transformers, Disconnects, Control Panels, All General Purpose Circuits
Fuse Class
Class RK1
Indicator
SmartSpot®
Insulation Material
PolyTube
Interrupt Rating
200 kAIC
Mounting Type
Clip
Rated Voltage AC
600 V
Rated Voltage DC
600 V
Tc Connection
Ferrule
Terminal Material
Tin-Plated Copper
Terminal Type
Ferrule
Type
Time-Delay
Voltage
600 VAC

Packaging

Pkg Qty
10

Manufacturer Information

Brand
Ferraz Shawmut Canada, Inc.
Sub Brand
Amp-Trap® 2000

General Product Info

12-Digit UPC
782001992019
Class
RK-1
Construction
Fiberglass
Product UPC
78200199201
Weight
0.34 lb

Dimensions

Diameter
1.06 Inch
Length
5-1/2 Inch
Features
  • Solid state SmartSpot visual blown fuse indicator
  • Time-delay for motor starting and transformer inrush currents without nuisance opening
  • 600VAC & 600VDC dual rated
  • 300kA interrupting rating - self-certified, UL witnessed tests
  • Extremely current-limiting for low peak let-thru current
  • Recommended for Arc Flash energy reduction
  • Easy 2-to-1 selectivity for prevention of nuisance shut downs and black outs
  • Rejection-style design prevents replacement errors (when used with recommended fuse blocks)
  • High-visibility orange label gives instant brand recognition
  • Reduced inventory by taking the place of class RK5, K, and H fuses
  • Metal-embossed date and catalog number for easier traceability and lasting identification
  • Fiberglass body provides dimensional stability in harsh industrial settings
Applications
  • Motors
  • Safety switches
  • Transformers
  • Branch circuit protection
  • Disconnects
  • Control panels
  • All general-purpose circuits
Approvals & Standards
  • UL listed to standard 248-12 File E2137
  • DC listed to UL standard 248
  • CSA certified to standard C22.2 No. 248.12